Hired-Hand Universal Ray Tube Heaters: AG1 Series User Manual
Page 5

Model Number
Mounting
Angle*
Sides
Front
Behind
Top**
Below
AG1 (20, 30, 40) - 50 [N, P]
0°
9
9
6
47
45°
39
8
10
47
with 1 side shield
0°
29
8
6
47
with 2 side shields
0°
9
9
6
47
20 ft. from burner
0°
7
7
6
30
AG1 (20, 30, 40) - 60 [N, P]
0°
9
9
6
47
45°
39
8
10
47
with 1 side shield
0°
29
8
6
47
with 2 side shields
0°
9
9
6
47
20 ft. from burner
0°
7
7
6
30
AG1 (20, 30, 40) - 75 [N, P]
0°
9
9
6
60
45°
39
8
10
60
with 1 side shield
0°
29
8
6
60
with 2 side shields
0°
9
9
6
60
20 ft. from burner
0°
7
7
6
30
AG1 (30, 40, 50) - 100 [N, P]
0°
14
14
6
66
45°
39
8
10
66
with 1 side shield
0°
29
8
6
66
with 2 side shields
0°
16
16
6
66
20 ft. from burner
0°
7
7
6
30
AG1 (40, 50) - 125 [N, P]
0°
20
20
6
76
45°
58
8
10
76
with 1 side shield
0°
42
8
6
76
with 2 side shields
0°
20
20
6
76
20 ft. from burner
0°
7
7
6
30
AG1 (40, 50, 60) - 150 [N, P]
0°
24
24
6
81
45°
58
8
10
81
with 1 side shield
0°
42
8
6
81
with 2 side shields
0°
23
23
6
81
20 ft. from burner
0°
11
11
6
44
5
1.0
Safety • Clearance to Combustibles
Chart 1.1 •
Clearance to Combustibles in Inches (see Figure 1.1 for Mounting Angles)
Figure 1.1
•
Mounting Angles
0° Mounting Angle
45° Mounting Angle
0° Mounting Angle
with 1 Side Shield
0° Mounting Angle
with 2 Side Shields
Side
Side
Below
Top
Front
Behind
Front
Behind
Side
Side
AG1
Series
* Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
** Maintain a 10 in. (0° mounting angle) or 12 in (1-45° mounting angle) clearance from ceilings constructed of tri-ply
plastic or plastic fogger lines.