Communication (serial) > basic settings, Communication (profibus-dp) – Yokogawa Button Operated DX2000 User Manual
Page 95
93
Installation and W
iring
Recommended Replacement
Periods for W
orn Parts
Setup Items and
Default V
alues
IM 04L42B01-02E
Communication (Serial) > Basic settings
Setup Item
Selectable Range or Selections
Default Value
Setting
Without /AS1
Baud rate
1200/2400/4800/9600/19200/38400
9600
Data length
7/8
8
Parity
Odd/Even/None
Even
Handshaking
Off:Off/XON:XON/XON:RS/CS:RS
Off:Off
Address
1 to 99
1
Protocol
Normal/Modbus/Modbus-M
Normal
With /AS1
*3
The baud rate, data length, parity, handshaking, address items are the same as on a DX without the /AS1 option.
Protocol
Normal/Modbus/Modbus-M/Barcode
Normal
Communication (Serial) > Modbus master > Basic settings
Setup Item
Selectable Range or Selections
Default Value
Setting
Read cycle
125ms/250ms/500ms/1s/2s/5s/10s
1s
Timeout
125ms/250ms/500ms/1s/2s/5s/10s/1min
1s
Retrials
Off/1/2/3/4/5/10/20
1
Inter-block delay
Off/5ms/10ms/15ms/45ms/100ms
Off
Auto recovery
Off/1min/2min/5min/10min/20min/30min/1h
2min
Communication (Serial) > Modbus master > Command settings
Setup Item
Selectable Range or Selections
Default Value
Setting
Master command number
1-8/9-16
1-8
1 to 16
First
Last
Addr.
Regi.
Type
Off/R/R-M/W/W-M/E-M
*3
Depends on the command type.
Depends on the command type.
1 to 247
Numerical value
INT16/UINT16/INT32_B/INT32_L/UINT32_B/
UINT32_L/FLOAT_B/FLOAT_L
Off
–
–
1
30001
INT16
Communication (PROFIBUS-DP)
*2
Setup Item
Selectable Range or Selections
Default Value
Setting
Node Address
0 to 125
3
Setup Items and Default Values