Meas channel > moving average – Yokogawa Button Operated DX2000 User Manual
Page 72
70
IM 04L42B01-02E
Setup Item
Selectable Range or Selections
Default Value
Setting
Mode=DI
Range
Span Lower
Span Upper
Level/Cont
0, 1
0, 1
Level
0
1
Mode=1-5V
Range
Span Lower
Span Upper
Scale Lower
Scale Upper
Unit
Low-cut
1-5V
0.800 to 5.200
0.800 to 5.200
–30000 to 30000, decimal position :0 to 4
–30000 to 30000, decimal position :0 to 4
6 characters or less
On/Off
1-5V
1.000
5.000
0.00
200.00
–
Off
Mode=Sqrt
Range
Span Lower
Span Upper
Scale Lower
Scale Upper
Unit
Low-cut
Low-cut value
20mV/60mV/200mV/2V/6V/20V/50V
Depends on the range.
Depends on the range.
–30000 to 30000, decimal position: 0 to 4
–30000 to 30000, decimal position: 0 to 4
6 characters or less
On/Off
0.0 to 5.0
–
–
0.00
200.00
–
Off
0.5
Alarm
1, 2, 3, 4
Type
Value
Relay
Number
Detect
On/Off
H:High/L:Low/h:delta H/l:delta L/R:rate H/
r:rate L/T:delayH/t:delayL
Numerical value
On/Off
I01/.../I06, I11/.../I16, I21/.../I26,
I31/.../I36 (Depends on the option.)
S01/S02/S03/.../S29/S30
On/Off
Off
H
–
Off
I01
On
Meas channel > Tag, Memory sample, Alarm delay
Setup Item
Selectable Range or Selections
Default Value
Setting
Without /AS1
First-CH, Last-CH
Channel number
001
Tag > Comment
*2
32 characters or less
*2
–
Tag > No.
*2
16 characters or less
–
Memory sample > On/Off
On/Off
On
Alarm delay > Time
1 to 3600
10
With /AS1
*3
The First-CH, Last-CH, Tag, and Memory sample items are the same as on a DX without the /AS1 option.
Alarm delay > Time
1 to 3600 when the unit is seconds. 1 to 24 when
the unit is hours.
10
Alarm delay > Unit
Hour/Sec
Sec
Meas channel > Moving average
Setup Item
Selectable Range or Selections
Default Value
Setting
First-CH, Last-CH
Channel number
001
Moving average > On/Off
On/Off
Off
Moving average > Count
2 to 400
2
Setup Items and Default Values