Setting measurement and recording conditions, Setting alarms – Yokogawa Touch Screen GP20 User Manual
Page 28
26
IM 04L51B01-02EN
Advanced Operation (Various settings and operation)
Setting Measurement and Recording
Conditions
Configuring the type of data to record to display data, the
scan interval to 2 s, and the trend interval to 1 min.
Setting the Type of Data to Record
Path
MENU key > Browse tab > Setting >
Setting menu >
Recording Settings >
Basic settings
1
2
1
Tap
File type > Display.
2
Tap
Save.
You can set the file type to record only the data that
suits your purpose. For example, you can record
detailed data or record data only when alarms occur.
For details, see the User’s Manual (IM 04L51B01-
01EN).
Setting the Scan Interval
Path
MENU key > Browse tab > Setting >
Setting menu >
Measurement settings >
Scan interval
1
2
1
Tap
Scan interval > 2s.
2
Tap
Save.
Operation complete
Setting the Trend Interval
Path
MENU key > Browse tab > Setting >
Setting menu >
Display settings > Trend
interval
1
2
1
Tap
Trend interval [/div] > 1 min.
2
Tap
Save.
Operation complete
Setting Alarms
On channel 1 of slot 0, set the high limit alarm at the alarm
value of 150°C.
Path
MENU key > Browse tab > Setting >
Setting menu >
AI channel settings > Alarm
1
2
3
4
5
6
1
Tap
First-CH > 0001.
2
Check that
Last-CH is 0001.
3
Tap
Level1 > On.
4
Tap
Type > H.
5
Tap
Value, and enter 150.0.
6
Tap
Save.
Operation complete
This section explains how to change various settings.
Before you change settings, stop recording and computation.