2 data mapping, 1 preparation, Data mapping -4 4.2.1 – Yokogawa GC1000 Mark II Process Gas Chromatograph User Manual
Page 17: Preparation -4

<4. Engineering>
4-4
IM 11B06E01-01E
4.2
Data mapping
4.2.1
Preparation
The IP addresses of analyzers, and mapping data of the Modbus address of analyzers onto the
address of ASGW, are defined in the ASGW_MAP.CSV file.
Mapping operation is complete when the file is transferred to ASGW with FTP and the ASGW is
rebooted.
ASGW checks the file at start-up. Information of error diagnosis is confirmed with Web browser.
At the installation on ASGW a sample file is setted. Mapping operation is realized with modifica-
tion of the sample file.
The mapping file does not depend on ASGW, so that the composition of mapped file is available
in advance without ASGW.
#SLAVE, 1
#RETRY, 3
**** Station
#STN,
10,
GC1000,
192.168.0.10,
GC1000Mk2 at SiteA
#STN,
42,
GC1000,
192.168.0.42,
GC1000Mk2 at SiteB
#STN, 101, ASIU,
192.168.0.101, ASIU
#STN, 252, PCAS,
192.168.0.252, PCAS
**** Mapping
#MAP, 10, 1001,
1,
RUN
#MAP, 42, 1002,
1,
RUN
#MAP, 10, 1004,
2,
STOP
#MAP, 42, 1005,
2,
STOP
#MAP,
252,
11001,
11010,
ID=10 A-ch Normal
#MAP,
252,
11002,
11042,
ID=42 A-ch Normal
#MAP,
252,
11004,
11310,
ID=10 B-ch Normal
#MAP,
252,
11005,
11342,
ID=42 B-ch Normal
#MAP,
101,
31002,
30401,
AI value of ASIU
**** Alarm DO ouput
#DO,
10,
ALM_LVL1,
12,
DO_12 output for alarm of Stn10
#DO,
10,
ALM_LVL2,
13,
DO_13 output for alarm of Stn10
#DO,
42,
ALM_LVL1,
3,
DO_3 output for alarm of Stn42
Example of mapping file
4th Edition : Nov. 22, 2011-00