<3. Functions>

3-1

IM 11B06E01-01E

3. Functions

ASGW has the following functions.

1. Interface to DCS through Modbus RTU Slave or Modbus TCP Server
2. Read and write data for multi-analyzers (GC1000 MarkII, ASIU)
3. Mapping analyzer data to ASGW Modbus data area
4. Alarm information

3.1

Interface to DCS

ASGW has 2 functions as an interface to DCS.

• Modbus TCP Server *
• Modbus RTU Slave (2 serial ports)

*: It requires Rev.1.01.04 or later for ASGW and Rev. 1.80 or for Stardom OS.

Modbus RTU uses two RS-232C communication ports. Both ports have the same functions. Two

communication ports can be used at the same time. Modbus RTU can be used with Modbus TCP

at the same time.

l

Max number of Client

When Modbus TCP Server is used, up to 4 clients (DCS) can be connected at the same time.

When the multiple clients request the same command, the last requested command is accepted.

3.2

Address mapping

ASGW assembles the data from multiple analyzers and sends it to the DCS.

Max. number of analyzers connectable: 31

Function

Available address for mapping Available points

GC1000 address area

Coil

01001 to 09000

8000

Coil, Input relay

Input relay

11001 to 19000

8000

Input relay

Holding register

41001 to 49000

8000

Input register, Holding register

Input register

31001 to 39000

8000

Input register

When the data address of analyzers is the coil or holding register, it is only possible to write to the

specific address.
Refer to the Modbus interface table in section 3.4.