<5. Parameter Summary>
5-9
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
SP setup
A/G Select
Gauge/Abs select for static
pressure
Gauge or Absolute
Absolute
WD
Atm. Pres Value
Conversion coefficient
101.3 kPa
WD
SP Apply values
Rerange for static pressure
“0%, 100%, or Exit”
MD
SP Damp
Damping time constant for SP
0.00 to 100.00
2.00 s
WD
SP H/L Select
H/L select for static pressure
High or Low
High
WD
SP Min Span
Minimum span for static pressure
RD
SP LRV
Lower range value for static
pressure
Within measurement range
0.0 MPa
WD
SP LSL
Lower sensor limit for static
pressure
RD
SP URV
*3
Upper range value for static
pressure
Within measurement range
WD
SP USL
Upper sensor limit for static
pressure
RD
Status
Device Status
Current operating status
R
Status group 1
Device status information for
hardware
Display the hardware error
R
Status group 2
Device status information for
hardware
Display the hardware error
R
Status group 3
Device status information for
process
Display the process error
(Out of specification)
R
Status group 4
Device status information for
process
Display the process error
(Out of setting range)
R
Status group 5
Device status information for
process
Display the process error
(Alarm)
R
Status group 6
Device status information for data
Display the setting error
R
Status group 7
Device status information for data
Display the setting error
R
Status group 8
Device status information for data
Display the diagnostic alarm
R
Status group 9
Device status information for data
Display the diagnostic alarm
R
Status group 10
HART 7
Device status information for data
Display the simulation mode
R
Ext dev status
HART 7
Extended Device Status
R
Time Stamp
Time Stamp
00:00:00
R
Tag
Tag
Tag number
8 alphanumerics
As specified
W
Long tag
HART 7
Long tag
Max 32 alphanumerics
As specified
W
Temperature
compensation
T.Z. Cmp mode
Temperature compensation mode
Off or On
Off
W
Temp Zero
Zero shift compensation
–99.999 to 99.999%/degC
0.000%/degC
W
Temperature
sensor
Amp temp
Amplifier temperature
R
Snsr temp
Capsule temperature
R
Transfer
function
Xfer fnctn
Output mode
Linear or Sq root
As specified or
Linear
W
Units
Unit
Pressure, Differential pressure unit
As specified or
kPa
W
SP Unit
Static pressure unit
MPa
WD
Temp Unit
Temperature unit
deg C, deg F, or Kelvin
deg C
W
Write
protection
menu
Enable wrt 10min
Write protection release
8 alphanumerics
M
New password
User set password for write
protection
8 alphanumerics
M
Write protect
Write protection indicator
Yes or No
No
R
*1:
Handling:
R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.