Yokogawa EJX115A User Manual
Page 85
<5. Parameter Summary>
5-7
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
Process Alerts Temp Hi Alert Val
High alert value for temperature
Set the threshold value for
high side alarm
120°C (deg C)
W
Temp Lo Alert Val
Low alert value for temperature
Set the threshold value for
low side alarm
-40°C (deg C)
W
Process
variables
Engr Disp
User scaled value
R
Engr Unit
User set engineering unit
Unit specified in Set Engr Unit
8 alphanumerics
R
Loop Current (DD)
AO (DTM)
HART 7
Loop current value
(Analog Output Current)
3.6 to 21.6 mA
R
Loop Current Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of Loop Current (mA)
Good
R
Loop Current Limit
Status
HART 7
Device variable limit status
Device variable limit status of
Loop Current (mA)
Not limited
R
PV (DD)
Pres (DTM)
Pressure/Differential pressure
value
R
PV (Pres) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of pressure
Good
R
PV (Pres) Limit
Status
HART 7
Device variable limit status
Device variable limit status of
pressure
Not limited
R
PV Update time
period (DD)
Update time period
(DTM)
HART 7
PV (Pres) Update time period
45 ms
R
% range (DD)
Pres % (DTM)
HART 7
Pressure value in %
-2.50 to 110.00%
R
% rnge (Percent
Range) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of % range (Percent
Range)
Good
R
% rnge (Percent
Range) Limit Status
HART 7
Device variable limit status
Device variable limit status of
% range (Percent Range)
Not limited
R
SV (DD), SP (DTM) Static pressure value
RD
SP %
Static pressure value in %
-10.0 to 100.00 %
RD
SV (SP) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of SV (SP)
Good
R
SV (SP) Limit
Status
HART 7
Device variable limit status
Device variable limit status of
SV (SP)
Not limited
R
SV Update time
period (DD)
SP update time
(DTM)
HART 7
SV (SP) Update time period
360 ms
R
*1:
Handling:
R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.