Yokogawa EJX115A User Manual
Page 43
<3. Parameter Setting>
3-30
IM 01C25T01-06EN
a. Burst Command
Select the transmission data at
Burst Command
parameter.
Burst Command
Command parameter
Cmd1: PV
PV (Pressure • Differential
Pressure)
Cmd2: % range/current % range/current (Percent of
range, Loop current)
Cmd3: Dyn vars/current Process vars/current
(Loop current, Pressure •
Differential Pressure • Static
Pressure • Temperature)
Cmd9: Device vars w/
status
Process vars/% range/current
Mapping by user
Cmd48: Read
Additional Device
Status
Self diagnosis information
b. Burst Variable Code/Device Variable Code
This parameter need to be set when
Burst
Command is Cmd9:Device vars w/status (up to
eight items).
• Procedure to call up the display
DD and DTM
[Root Menu] → Detailed setup
→Output condition →HART output
→ Burst condition → Burst Message
1,2 or 3 → Burst Device Variables
→ Burst Variable Code (DD)/Device
Variable Code (DTM) →
Display Item
Contents
PV
Select the pressure
SV
Select the static pressure
TV
Select the capsule temperature
% rnge
Select the % output
Loop current
Select the output current
Not Used
–
c. Update period and Max Update Period
Set to
Update Period and Max Update Period.
When the period that is earlier than the operation
period of each process value was set, it is set
automatically to become bigger than an operation
period of the transmitter.
For
Update Period, set the value that is smaller
than
Max Update Period.
• Procedure to call up the display
DD and DTM
[Root Menu] → Detailed setup
→Output condition →HART
output → Burst condition → Burst
Message 1,2 or 3 → Set Burst
Period
→ Update Period
/ Max Update
Period
0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min
d. Burst Msg Trigger Mode
Set the
Burst Msg Trigger Mode from the
parameters shown below.
When
Burst Msg Trigger Mode is Window, Rising
or Falling, set the
Burst Trigger Level.
• Procedure to call up the display
DD and DTM
[Root Menu] → Detailed setup →
Output condition →HART output →
Burst condition → Burst Message 1,2
or 3 → Set Burst Trigger →
Display Item
Contents
Continuous
Burst Message is transmitted
continuously.
Window
In “Window” mode, the Trigger Value
must be a positive number and is the
symmetric window around the last
communicated value.
Rising
In “Rising” mode, the Burst Message
must be published when the source
value exceeds the threshold
established by the trigger value.
Falling
In “Falling” mode, the Burst Message
must be published when the source
value fall below the threshold
established by the trigger value.
On-change
In “On-change” mode, the Burst
Message must be published when the
source value on change established