Parameter summary, Parameter summary -1 – Yokogawa EJX115A User Manual
Page 79
<5. Parameter Summary>
5-1
IM 01C25T01-06EN
5. Parameter Summary
Function
Label
Item
Contents
Default value Handling
*
1
Analog output AO alm typ
Analog output alarm type
High or Low
R
AO lower limit
Lower limit of analog output
3.6000 to 21.6000 mA
3.6000 mA
W
AO upper limit
Upper limit of analog output
3.6000 to 21.6000 mA
21.6000 mA
W
Auto recover
Auto-recover from hardware error
Off or On
On
W
Analog output
trim
Clear D/A trim
Reset analog output trim
M
D/A trim
Analog output trim with ammeter
M
Scaled D/A trim
Analog output trim with voltmeter
M
Channel flags
Analog channel flags
0x00
R
Bi-directional
mode
Bi-dir mode
Bi-directional mode
Off or On
Off
W
Burst mode
Burst mode
Burst mode *
2
Off or On
HART 5
Off or Wired HART Enabled
HART 7
Off
W
Burst option
HART 5
Burst option
Xmtr Variables, PV, % range/
current, Process vars/crnt
W
Burst Command
HART 7
Burst Command *
2
Cmd 1: PV
Cmd 2: % range/current
Cmd 3: Dyn vars/current
Cmd 9: Device vars w/status
Cmd 48: Read Additional
Device Status.
Cmd 1: PV
W
Burst Variable
Code (DD)
Device Variable
Code (DTM)
HART 7
Device Variable for the Burst
Message *
2
Max 8 slots.
W
Burst Msg Trigger
Mode
HART 7
Burst Trigger Mode Selection Code
*
2
(Continuous, Window, Rising,
Falling, On-change)
Continuous
R
Set Burst Trigger
HART 7
Configure burst trigger
Configure Burst Msg Trigger
Mode and Burst Trigger Level
M
Set Burst Period
HART 7
Configure burst period
Configure Update Period and
Max Update Period
M
Burst Trigger Level
HART 7
Burst Trigger Level *
2
0.0
R
Update Period
HART 7
Update Period for Burst mode *
2
Update period for burst
message
Burst Message
1: 0.5s
2: 60s
3: 60s
R
Max Update Period
HART 7
Max Update Period for Burst mode
*
2
Maximum update period for
burst message
60 min
R
Damping
Pres Damp
Damping time constant for DP
0.00 to 100.00 s
W
Quick resp
Quick response
On or Off
Off
W
Date
Date
Date
**/**/**
W
Descriptor
Descriptor
Descriptor
16 alphanumerics
W
*1:
Handling:
R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.