beautypg.com

Chapter 6, Appendix, Specifications – Watlow Series PD Ethernet Enabled Temperature and Process Controller User Manual

Page 26

background image

W a t l o w S e r i e s P D

2 4

A p p e n d i x

Specifications

(2341)

Controller
• Microprocessor based user-selectable control

modes

• Single or dual channel universal inputs
• Current transformer inputs to monitor heater cur-

rents

• Digital inputs
• Up to four programmable outputs
• Update rates, inputs = 10Hz, outputs = 10Hz
Operator Interface
• Browser based HMI (human machine interface)
Standard Conditions For Specifications
• Ambient temperature 25°C (77°F) ±3°C, rated line

voltage, 50 to 60Hz, 0 to 90% RH non-condensing,
15-minute warm-up

Universal Analog Input
• Sample rate: 10 Hz

Thermocouple

• Type J, K, T, N, E, C, (W5), D (W3), PTII (F), R, S,

B thermocouple types.

• >20 M

input impedance

• Maximum 20

source resistance

RTD

• 2- or 3-wire platinum, 100

• DIN curve (.00385 curve)
• 250 µA nominal RTD excitation current

Process

• Range selectable: 0 to 10VÎ (dc), 0 to 20 mA. (Can

reverse low and high values.)

• Voltage input impedance 20 k

• Current input impedance 100

• Minimum current source resistance 1 M

• Input resolution 25,000 bits (approximately) at full

scale

Input Accuracy Span Ranges

Thermocouple Input
• Calibration accuracy and sensor conformity: ±0.1%

of input span ±1°C at standard conditions

• Temperature stability: ±0.2 degree per degree

change in ambient for J, K, T, N, E, PTII
±0.5% for C, D, R and S

RTD Input
• Calibration accuracy ±0.1% of input range ±1°C at

standard conditions

• Temperature stability: ±0.05 degree per degree

change in ambient

Process Input
• Voltage input ranges

Accuracy ±10mV ±1 LSD at standard conditions
Temperature stability ±100 ppm/°C maximum

• Milliamp input ranges

Accuracy ±20µA ±1 LSD at standard conditions
Temperature stability ±100 ppm/°C maximum

Digital Input
• Contact closure or voltage input
• Input impedance:10 k

• Sample rate: 5 Hz
• Resistance/contact input

Input high state >7 k

Input low state 0-2 k

• Voltage input

Input high state 2-36 VdcÎ
Input low state 0-1 VdcÎ

Current Transformer Input
• Input range: 0-50 mA‡ (ac)
• Input impedance:100

• Sample rate: 5 Hz

Allowable Operating Ranges

Type J:

-210 to 1,200°C or -346 to 2,192°F

Type K:

-270 to 1,372°C or -454 to 2,502°F

Type T:

-270 to

400°C or -454 to

752°F

Type N:

-270 to 1,300°C or -454 to 2,372°F

Type E:

-270 to 1000°C or -454 to 1,832°F

Type C:

0 to 2,315°C or

32 to 4,200°F

Type D:

0 to 2,315°C or

32 to 4,200°F

Type PTII (F):

-3 to 1,396°C or

25 to 2,545°F

Type R:

-50 to 1,767°C or -58 to 3,214°F

Type S:

-50 to 1,767°C or -58 to 3,214°F

Type B:

0 to 1,820°C or

32 to 3,308°F

DIN

-200 to

800°C or -328 to 1,472°F

Process

-1,999 to

9,999 units

Type J:

0 to

750°C or

32 to 1,382°F

Type K:

-200 to 1,250°C or

-328 to 2,282°F

Type T:

-200 to

350°C or

-328 to

662°F

Type N:

0 to 1,250°C or

32 to 2,282°F

Type E:

-200 to

800°C or

-328 to 1,470°F

Type C (W5):

0 to 2,315°C or

32 to 4,200°F

Type D (W3):

0 to 2,315°C or

32 to 4,200°F

Type PTII (F):

0 to 1,393°C or

32 to 2,540°F

Type R:

0 to 1,450°C or

32 to 2,642°F

Type S:

0 to 1,450°C or

32 to 2,642°F

Type B:

870 to 1,700°C or 1,598 to 3,092°F

RTD (DIN):

-200 to

800°C or

-328 to 1,472°F

Process:

-1,999 to 9,999 units

Appendix

6