beautypg.com

Output 4, Output 3 open collector, Output 3 process – Watlow Series PD Ethernet Enabled Temperature and Process Controller User Manual

Page 19: Output 4 mechanical relay, Figure 17a, Figure 17b, Figure 17c

background image

W a t l o w S e r i e s P D

17

C h a p t e r 2 I n s t a l l a n d W i r e

ç

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.

Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.

Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.

Note: A current transformer input
is not available if Output 1 or 3
is a process output.

Figure 17a —

Output 3 Open Collector

PD_ _ - _ _ C _ - _ _ _ _

• Maximum current sink 250 mAÎ (dc)

• Maximum supply voltage 42VÎ (dc)

• Output does not supply power

Figure 17b —

Output 3 Process

PD_ _ - _ _ F _ - _ _ _ _

• Analog output scalable from 0 to 10VÎ (dc) or 0 to 20 mAÎ (dc)

• Load capability: voltage, 1 k

minimum; current, 800

maximum

• Output supplies power

• Cannot use voltage and current output at the same time

Figure 17c —

Output 4 Mechanical Relay

PD_ _ - _ _ _ E - _ _ _ _

• Form C.contacts

• 2 A, resistive

• 125 VA pilot duty, 120/240VÅ (ac), inductive

• 240VÅ (ac) maximum

• 30VÎ (dc) maximum.

• See Quencharc note

• For use with ac or dc

• Minimum load current: 10 mA

• Output does not supply power

Internal Circuitry

COM.

N.O.

Mechanical Relay

23

24

N.C.

22

22 23 24

24 normally open

23 com

22 normally closed

19 20 21

21 amps +

19 volts +

20 com -

Internal Circuitry

dc-

COM.

dc+

42VÎ (dc) maximum

Open Collector

19

21

20

Load

-

+

Power

Supply

-

+

Class 2 power source
required for agency
compliance.

19 20 21

21 DC -

19 DC +
20 com