Wa t l o w S e r i e s C

• 7 •

C h a p t e r 3 W i r i n g

ç

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may
result in damage to equipment
and property, and/or injury or
loss of life.

Ó

WARNING: If high voltage is ap-
plied to a low-voltage controller,
irreversible damage will occur.

Note: Insulated terminals re-
quired for quick connect style
terminals.

For quick connect terminals 1,
2, 6, 7, 8, 9, and 10, AMP P/N
3-520406-2 or equivalent recom-
mended. Use Amp crimp tool
P/N 58078-3, insert 90391-3.

For quick connect terminals 3, 4,
and 5, AMP P/N 2-520405-2 or
equivalent recommended. Amp
crimp tool P/N 58078-3, insert
58079-3.

Note: To prevent ground loops,
isolation needs to be maintained
from input to output when us-
ing a switched DC output. Un-
grounded thermocouples recom-
mended.

Figure 7a —

AC Power Wiring

• Nominal voltage options:

- 24V

Å (ac)

- 120V

Å (ac)

- 230 to 240V

Å (ac)

L1

L2

L1

L2

1

2

3

4

5

6

10

9

8

7

Figure 7b —

Thermocouple Input

Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to TC-.

• Input impedance: >10 M

Ω

TC+

TC

-

Thermocouple

-

Thermocouple +

1

2

3

4

5

6

10

9

8

7

Figure 7c —

RTD Input

(100

Ω Platinum DIN curve 0.00385 Ω/Ω/°C)

• Terminals S2 and S3 must be shorted for a two-wire RTD

• Nominal excitation current: 125 μA

S2

S1

RTD S1

RTD S2

S3

S3

RTD S1

RTD S2
RTD S3

2-Wire RTD

3-Wire RTD*

*No lead resistance
compensation

1

2

3

4

5

6

10

9

8

7