Watlow Series TM User Manual
Page 15

Wa t l o w S e r i e s C
• 1 3 •
C h a p t e r 4 U s e r I n t e r f a c e
To adjust the Calibration Offset on models with tactile 
keys, first hold down both the Increment and Decre-
ment keys for five seconds. The display will first show 
[`CAL] for five seconds, then it will display the Cali-
bration Offset value. Adjust the value with the Incre-
ment and Decrement keys (range: -30 to 30°). The new 
value will take effect three seconds after the last key 
stroke. The display will blink, then return to the pri-
mary display after five seconds.
To change the temperature units on models with 
tactile keys, first hold down both the Increment and 
Decrement keys for ten seconds. The display will show 
[F``C] for two seconds. Adjust the units with the In-
crement and Decrement keys. The new value will take 
effect three seconds after the last key stroke. The dis-
play will blink, then return to the primary display after 
five seconds. The set point value, process value and 
offset will automatically adjust to the new temperature 
scale.
F
C
LOAD
CV
PUSH
TO SET
LED Display:
Indicates
the process value until 
the Push to Set Key is 
operated.
PUSH TO SET Key:
The process value (Actual 
Temperature) is displayed 
when this key is not 
operated. When this key is 
depressed, the set point is 
displayed and can be 
adjusted.
LOAD Indicator Light:
Lit
when output is energized.
F or C Indicator Light:
Lit
to indicate if unit is configured 
for degrees Fahrenheit or 
degrees Celsius.
Set Point Knob:
To increase
set point, turn knob clockwise. 
To decrease set point, turn 
knob counterclockwise. The 
new set point is entered 3 
seconds after the knob stops 
moving.
Variable Set Point, Push to Set
CV _ (1, 2, 5 or 6) _ _ _ _ _ _ _ _ _ _ D
Finger Tip Indent:
Insert
finger tip into indent for 
quick and easy set point 
changes.
Figure 13a — Variable 
Set Point, Push to Set In-
terface
F
C
LOAD
CV
PUSH TO
SET
LED Display:
Indicates
the process value until 
the Push to Set Key is 
operated.
PUSH TO SET Key:
The process value (Actual 
Temperature) is displayed 
when this key is not 
operated. When this key is 
depressed, the set point is 
displayed and can be 
adjusted.
LOAD Indicator Light:
Lit
when output is energized.
F or C Indicator Light:
Lit
to indicate if unit is configured 
for degrees Fahrenheit or 
degrees Celsius.
Variable Set Point, Push to Set
CV _ (A, B, C or D) _ _ _ _ _ _ _ _ _ _ D
Increment and Decrement Keys: 
Press the Up-Arrow key to 
increase the set point. 
Press the Down-Arrow key to 
decrease the set point.
The new set point is entered 3 
seconds after the last key stroke.
Figure 13b — Variable 
Set Point, Push to Set In-
terface with Tactile Keys