Wa t l o w S e r i e s C

• 8 •

C h a p t e r 3 W i r i n g

ç

Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.

Note: Insulated terminals re-
quired for quick connect style
terminals.

For quick connect terminals
1, 2, 6, 7, 8, 9, and 10, AMP
P/N 3-520406-2 or equivalent
recommended. Use Amp
crimp tool P/N 58078-3, in-
sert 90391-3.

For quick connect terminals
3, 4, and 5, AMP P/N 2-
520405-2 or equivalent rec-
ommended. Amp crimp tool
P/N 58078-3, insert 58079-3.

Quencharc Note:
Switching pilot duty loads
(relay coils, solenoids, etc.)
with the mechanical relay
output options requires use
of an R.C. suppressor.

Watlow carries the R.C. sup-
pressor Quencharc brand
name, which is a trademark
of ITW Paktron. Watlow Part
No. 0804-0147-0000.

Figure 8a —

Switched DC Output

• Maximum voltage output into an infinite load, 24V

Î (dc)

• Minimum output voltage at 10 mA, 5V

Î (dc)

• Minimum load impedance, 500

Ω

• Offstate leakage, 100μA

Î (dc)

• Not recommended for switching mechanical relays

• Output supplies power

SWDC

-

SWDC+ Switched DC+

Switched DC

-

+

-

External
Load

Internal Circuitry

SWDC

-

SWDC+

17V

(dc) unreg

Switched DC

300

Ω

300

Ω

1

2

3

4

5

6

10

9

8

7

Figure 8b —

Mechanical Relay Output

• Form C contacts

• 8 A, resistive

• 250 VA pilot duty, 120/240V

Å (ac), inductive

• 240V

Å (ac) maximum

• 30V

Î (dc) maximum

• See Quencharc note

• For use with ac or dc

• Minimum load current 100 mA

• Output does not supply power

Internal Circuitry

COM.

N.O.

Mechanical Relay

N.C.

C

N.C.

N.O. Normally Open

Common

Normally Closed

L1

L2

External

Load

Customer supplied Quencharc

for pilot duty, inductive loads

only. See note.

1

2

3

4

5

6

10

9

8

7