beautypg.com

Troubleshooting – Watlow Series TM User Manual

Page 17

background image

Wa t l o w S e r i e s C

• 1 5 •

Tr o u b l e s h o o t i n g

Troubleshooting

Indication

Probable Cause(s)

Corrective Action

On indicating controls, the
display is not illuminated.

• Power supply switch off.

• Turn switch on.

• Fuse blown.

• Replace fuse (check cause of failure).

• Breaker tripped.

• Reset breaker (check cause of failure).

• Safety interlock door switch activated. • Close door.

• Separate system limit control latched.

• Reset limit controller.

• Wiring incorrect or open.

• Check wiring.

• Power supply voltage incorrect.

• Verify input power.

• Defective controller.

• Repair or replace controller.

Troubleshooting thermocouple inputs

Temperature reading is
incorrect, showing a sen-
sor error,

[Er;In] , or LOAD

LED is switching at the
wrong temperature.

• Calibration offset is incorrect (tactile
models only).

Check calibration offset.

• Settings for degree C or F is incorrect.

Check model part number for degree C or F.
If model has Increment/Decrement keys then
C/F setting is adjustable.

• Sensor or controller may be bad.
Sensor connections may be bad.

• Place a jumper wire across the thermo-
couple input terminals. The display should
indicate ambient temperature. If it does, the
controller is OK.

For controllers without the ability to view
process temperature:

- Decrease set point below ambient tempera-
ture, LOAD LED should be off for heating
controllers and on for cooling controllers.

- Increase set point above ambient tempera-
ture. LOAD LED should be on for heating
controllers and off for cooling controllers.

• Ambient temperature in the control
cabinet is over 70°C.

• Measure temperature in cabinet to ensure
it is below 70C. Vent cabinet or add fans if
necessary.

• Ground loop problem. Can occur
when using a switched DC output and
a grounded thermocouple.

• Remove power from the system. Use an
ohm meter to measure resistance between
output DC- and the thermocouple sheath. If
there is continuity, replace sensor with an
ungrounded thermocouple.

Temperature reading is de-
creasing, but actual process
is increasing.

• Thermocouple polarity is reversed. In
the US, red wire insulation denotes the
negative wire.

• Check thermocouple connections. All con-
nections, including extension wire must
maintain the correct polarity. Correct polarity
problems.

Temperature reading is
reading low and not increas-
ing while actual process
temperature is increasing.

• Sensor is bad. Thermocouple is short-
ed.

• Check thermocouple connections. Check
thermocouple wire insulation to make sure
it is not damaged, causing the wires to short
(making a new junction).

Temperature reading is
offset from actual process
temperature, or the output
switches on or off at the
wrong temperature. The off-
set changes with changes in
process temperature.

• Copper wire was used instead of ther-
mocouple extension wire. Connectors
of metals different than thermocouple
metal were used to splice or make con-
nections.

• Check thermocouple connections. Check to
make sure that only thermocouple extension
wire of the correct type was used to extend
thermocouple leads. Replace if necessary.

This manual is related to the following products: