9

Install and Wire, Chapter 2

WATLOW Series 942 User's Manual

Input Wiring

Figure 9 -
2 or 3 wire RTD
Input Wiring.

Figure 8 -
Thermocouple
Input Wiring.

Long lead lengths create electrical resistance. There will be approximately +2

°

C input error

for every 1

of lead length resistance, when using a two wire RTD. The resistance, when

added to the resistance of the RTD element, will result in erroneous input to the instrument.
To overcome this problem, use a three wire RTD sensor, which compensates for lead length
resistance. When extension wire is used for a three wire RTD, all three extension wires
must have the same electrical resistance. (i.e. same gauge, copper stranded).

RTD, 2 or 3 Wire

Model # 942A -

2

_ _ _ - _ 000

942A -

3

_ _ _ - _ 000

Thermocouple Input

Model # 942A -

1

_ _ _ - _ 000

942A -

3

_ _ _ - _ 000

942A -

2

_ _ _ - _ 000

942A -

4

_ _ _ - _ 000

+

-

7

9

You must use an isolated or ungrounded thermocouple, if an external device with a non-
isolated circuit common is connected to the 4-20mA or 0 - 5VDC output.

Extension wire for thermocouples must be of the same alloy as the thermocouple itself to
limit errors.

4
5
6

4
5
6

Jumper #5 to #6