Wiring example, System wiring example – Watlow Series 942 User Manual

Page 20

background image

Install and Wire, Chapter 2

20

WATLOW Series 942 User's Manual

Terminal Function

1 Not Used
2 Not Used
3 Not Used
4 Not Used
5 Not Used
6 Not Used
7 T.C. +
8 Not Used
9 T.C. -
10 L1 240V
11 L1 120V
12 L2
13 Earth Ground
14 N.O.
15 Com.
16 Com.
17 N.O.
18 N.C.

Output #1

Output #2

945A-2DD0-A000

Wiring Example

Figure 30 -
System Wiring
Example

CAUTION:

All wiring and fusing must conform to the National Electric Code NFPA70. Con-
tact your local board for additional information. Failure to observe NEC safety
guidelines could result in injury to personnel.

WARNING:

Watlow mercury relays are designed to be used only with resistive loads.

942A-1DD0-A000

Integral Setpot

140A-16XX-6000

High Limit Control

(-)

(+)TC Input

L1

L1

L2

Type "J"

Thermocouple

Fuse

Mercury

Relay for

Control

L2

Fuse

Load
Power

L2

High Limit

Control Power

120 VAC

Indicator ON

when limit trips

High Limit
Mechanical
Contactor

Limit Sensor

Process Sensor

Coil

π

Heat
Load

945A-2DD0-A000

Temperature Control

Earth Ground

L1
L2

(+)

(-)Red

Normally Open

Momentary Switch

9

7

11
12
13

Fuse

L1

14
15

16
17

T/C

T/C

ControlPower

120 VAC

L2

Indicator ON when

limit trips

942A-1DD0-A000

Temperature Control

!

!