WATLOW Series 942 User's Manual

Appendix

NOTE:
An X applies to
either Hysteresis 1,
2, 3, or 4.

Specifications

Appendix 1

Control Mode

24 step ramping control or programmer.

Simple, non-ramping set point.

Single input, dual outputs.

Optional dual auxiliary outputs, selectable as alarms or time based events.

Optional retransmit of set point or process variable.

RS-422A, RS-423A, or EIA-485 data communications available.

Control outputs: User selectable as: Heat, Heat/Cool, Cool, Cool/Heat

Outputs independent, related via dead band for Heat/Cool.

ON/OFF: Selectable per Outputs 1 and 2.

Proportional band: 0 to 999

°

F/0 to 555

°

C/0 to 999 Units or % of span

Reset: 0.00 to 9.99 repeats per minute.
Integral: 0 and 00.1 to 99.9 minutes per repeat.
Rate/Derivative: 0.00 to 9.99 minutes.
Cycle time: 1 to 60 seconds.

Dead band:

±

99

°

F,

±

55

°

C or

±

99 Units

(

±

9.9

°

F,

±

5.5

°

C or

±

9.9 units for rtd.1 and process units)

Operator Interface

Membrane front panel.

Dual, four digit 0.56" (14 mm) LED displays.

MODE, HOLD/RUN, UP, and DOWN keys.

Input

Thermocouple, RTD, and electrical process input.

Automatic cold junction compensation for thermocouple.

RTD input 2 or 3 wire, platinum, 100 ohm @ 0

°

C, software selectable:

JIS curve #3916 (0.003916

/

/

°

C) or DIN curve #3850 (0.003850

/

/

°

C).

Sensor break protection de-energizes control outputs to protect system.

Grounded or ungrounded sensors.

°

F,

°

C, or process variable units are user selectable.

J t/c:

32

to 1382

°

F

or

0

to

750

°

C

K t/c:

-328 to 2282

°

F

or -200

to 1250

°

C

T t/c:

-328 to

662

°

F

or -200

to

350

°

C

N t/c:

32 to 2282

°

F

or

0

to 1250

°

C

C t/c:

797 to 4200

°

F

or

425

to 2315

°

C

PT 2 (Platinel 2) 32 to 2543

°

F

or

0

to 1395

°

C

R t/c:

32 to 2642

°

F

or

0

to 1450

°

C

S t/c:

32 to 2642

°

F

or

0

to 1450

°

C

*B t/c:

*32 to 3092

°

F

or

0

to 1700

°

C

1

°

RTD:

-328 to 1112

°

F

or -200

to

600

°

C

0.1

°

RTD:

-99.9 to 392.0

°

F

or -99.9

to 200.0

°

C

0-5VDC:

-500 to 3500 Units

4-20mA:

-500 to 3500 Units

Primary Output (Heating or Cooling)

Solid state relay, Form A 0.5A @ 24VAC min., 264VAC maximum, opto-
isolated, zero cross switching. Off state impedance is 20K

minimum for

942A-XBXX-X0000 units, and infinite impedance for 942A-XKXX-X000 units.

Electromechanical relay, Form C, 6A @ 120/240VAC, 6A @ 28VDC,
1/8 hp. @ 120VAC, 125VA @ 120VAC. Off state impedance is 20K

min.

Switched DC Open collector, 500

minimum load resistance, 1K

load,

9mA minimum, 22mA maximum, non-isolated.

0-20mA or 4-20mA reverse or direct into a 600

maximum load impedance,

non-isolated.

0-10VDC or 0-5VDC reverse or direct into a 1K

minimum load impedance,

non-isolated.

* B t/c: Useable
range is suggested
to be 1598 to 3092

°

F

or 870 to 1700

°

C.

Range is at 32

°

to

allow using at low
temperatures
without range low
sensor errors.