beautypg.com

Operation, Operation menu and parameters, The operation menu – Watlow Series 942 User Manual

Page 28: Operation parameters, Operation menu

background image

Setup, Chapter 4

28

WATLOW Series 942 User's Manual

Operation

Operation Parameters

Set Point: Sets the operating set point for the control outputs. "SP" does not
appear, the control set point value will. Decrementing the set point below rL
displays OFF in the lower display. This disables all outputs except deviation alarm
outputs, which remain energized.
Range: OFF/ rL to rH

Default: Dependent on input range

Program: Select whether you want to enter the Program menu or enter the
Operation menu. By selecting no, you continue to the Operation menu.
Range: YES or no

Default: no

Ent1: Select whether Event 1 ( Output 3) is ON or OFF. When a profile is com-
plete or has been put on hold, it holds at its previous state. Only appears if Ot3 =
Ent, and your unit has auxiliary outputs. For more information on events see
Chapter 6.

Range: On or OFF

Default: OFF

[

SP ]

Prog (no)

Ent1

Operation Menu

In the Operation menu, the 942 operates as a digital set point control. Select a set
point and the 942 attains that value on a non-linear ramp. If your unit has auxiliary
outputs programmed as events, they can be selected as ON or OFF. All outputs
are turned OFF when set point is set to OFF.

M

Mode Key

= Parameter may or may not appear

depending on control configuration.

Figure 34 -
The Operation Menu.

NOTE:

The Upper display
always returns to
the process value
after 1 minute
without key strokes.

Pb1

Pb2

rE1/It1

rE2/It2

rA1/dE1

rA2/dE2

ct1

ct2

db

A1LO

A1HI

A2LO

A2HI

CAL

Aut

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

Ent1

Ent2

( )

( )

[SP]

Prog

(no)

Event 1

Event 2

Proportional band 1

Proportional band 2

Reset 1/Integral 1

Reset 2/Integral 2

Rate 1/Derivative1

Rate 2/Derivative 2

Cycle time 1

Cycle time 2

Deadband

Alarm 1 low

Alarm 1 high

Alarm 2 low

Alarm 2 high

Calibration offset

Auto-tune

[Set Point]

Program?