Four dashes, "- - - -", in the upper display indicate a Series 942 error.

• The error code is visible in the lower display.

Error code definitions and actions…

Er 1

- Sensor overrange error

The sensor input generated a value that was higher than that allowed for the
range of the sensor, or the A/D circuitry malfunctioned. Enter a valid input.
The A/D value is above the range limits, but within the A/D conversion limits.
Make sure the In parameter matches your sensor.

Er 2

- Sensor underrange error

The sensor input generated a value that was lower than that allowed for the
range of the sensor, or the A/D circuitry malfunctioned. Enter a valid input.
The A/D value is below the range limits, but within the A/D conversion limits.
Make sure the In parameter matches your sensor.

Er 3

- Ambient error

Check the specification for the ambient temperature range.

Er 4

- Configuration error

The unit's microprocessor is faulty; call the factory.

Er 5

- Non volatile checksum error

The nonvolatile memory checksum discovered a checksum error. Unless a
momentary power interruption occurred while the unit was storing data, the
nonvolatile memory is bad. Call the factory.

Er 6

- A/D underflow error

The A/D circuit is underrange. An open or reversed polarity sensor is the
most likely cause. Check the sensor; if the connection is good, and the
sensor functions properly, call the factory. The A/D underrange voltage is
too low to convert an A/D signal. Make sure the In parameter matches your
sensor.

Er 7

- A/D overflow error

The A/D circuit is overrange. An open or reversed polarity sensor is the
most likely cause. Check the sensor; if the connection is good, and the
sensor functions properly, call the factory. The A/D underrange voltage is
too high to convert an A/D signal. Make sure the In parameter matches your
sensor.

Error Codes

Figure 41 -
Error Code Display
Example

WARNING:

Electrical noise or a
noise event, vibra-
tion or excess
environmental
moisture or tem-
perature may cause
Series 942 errors to
occur. If the cause
of an error is not
otherwise apparent,
check for these.

!

!