beautypg.com

Output 2 wiring, S.s. relay, output 2 wiring diagram, Dc (open collector), output 2 wiring – Watlow Series 942 User Manual

Page 15

background image

15

Install and Wire, Chapter 2

WATLOW Series 942 User's Manual

Output 2 Wiring

Solid State Relay With Contact Suppression, Output 2

Model # 942A - _ _

B

_ - _ 000

COM.

N.O.

External

Load

Fuse

L1

L2

15

14

Solid State Relay, Form A, 0.5 Amp

L1

L2

Solid State Relay With Contact Suppression
Watlow's solid state relay changes state at zero volts, which is "zero-cross switching." They
are also optically isolated, which means the output circuitry is energized by infrared light
striking a photosensitive device. This results in a virtual absence of electrically generated
noise, and provides electrical isolation between the input and output. For use in switching
mercury relays or small AC loads. Off state impedance is 20K

minimum.

Switched DC Output (Open Collector), Output 2

Model # 942A - _ _

C

_ - _ 000

Figure 20 -
Solid State Relay
With Contact
Suppression,
Output 2 Wiring.

Switched DC
Watlow's solid state switch is a low current DC output (open collector) used to switch an
external power switching device such as a SSR or an electromechanical relay. The input
specifications of the power switching device must match those listed for the S.S. switch
output. The power switching device must provide isolation between the S.S. switch output
and load power since the S.S. switch output is a non-isolated output. Minimum load
resistance is 500

. Available current is 9mA minimum and 22mA maximum.

15

14

Switched DC, Open Collector, Non-Isolated

Logic

Switch

External

Load

-

+

+

-

NOTE:
This output is sup-
plied with an arc
suppression snub-
ber across the out-
put terminals. High
impedance loads
may remain ener-
gized even though
the output device is
turned OFF.

Figure 21 -
Switched DC Output
(Open Collector),
Output 2 Wiring.