Setup, Chapter 4

30

WATLOW Series 942 User's Manual

Operation

Operation Parameters

Value

Range

Factory Default

SP

OFF/rL to rH

75

°

F

Prog

YES or no

no

Ent1

On or OFF

OFF

Ent2

On or OFF

OFF

Pb1

If dFL = US: 0 - 999

°

F/0 - 555

°

C/0 - 999 Units

25

°

F

0 - 99.9

°

F/0 - 55.5

°

C/0 - 99.9 Units

If dFL = SI: 0 to 999.9%

3.0%

0 = ON/OFF control. HYS1 = switch. diff.

Pb2

Same as Pb1. Will not appear if Ot 2 = no.

0

°

rE1/It1

Reset: 0.00 to 9.99 repeats/min.

0.00 repeats/min.

Integral: 0 and 00.1 to 99.9 min./repeat
0.00 = no reset. Will not appear if Pb1 = 0.

rE2/It2

Same as rE1. Will not appear if Pb2 = 0.

0.00 repeats/min.

rA1/dE1

0.00 to 9.99 min.

0.00 min.

0.00 = No Rate. Will not appear if Pb1 = 0

rA2/dE2

Same as rA1. Will not appear if Pb2 = 0.

0.00 min.

Ct1

1 to 60 seconds

5 seconds

Won't appear if Pb1 = 0, or output 1 is 4-20

Ct2

1 to 60 seconds

5 seconds

Will not appear if Pb2 = 0 or Ot2 = no.

db

±

0 - 99

°

F/

±

0 - 55

°

C/0 - 99 Units.

0

±

0.0 - 9.9

°

F/0.0 - 5.5

°

C/0.0 - 9.9 Units

Appears if ht/CL or CL/ht.

A1LO - Deviation dE

-999

°

to 0

°

-999

°

Process Pr

rL to A1HI

rL

Appears if auxiliary output and Ot3 = AL.

A1HI - Deviation dE

0

°

to 999

°

999

°

Process Pr

A1LO to rH

rH

Appears if auxiliary output and Ot3 = AL.

A2LO-

Deviation dE

-999

°

to 0

°

-999

Process Pr

rL to A2HI

rL

Appears if auxiliary output and Ot4 = AL.

A2HI-

Deviation dE

0

°

to 999

°

999

°

Process Pr

A2LO to rH

rH

Appears if auxiliary output and Ot4 = AL.

CAL

±

99

°

F/

±

55

°

C/

±

99 Units

0

AUt

0 to 3

0

Table 3 -
Operation Menu Parameters and Descriptions.

Alarm 1 High: This parameter represents the high process alarm or high deviation
alarm for Alarm 1. This parameter appears if your unit has an auxiliary output and
Ot3 = AL. See the model number. If AL 1 = Pr: Range: A1LO to rH Default: rH
AL 1 = dE: Range: 0 to -999

°

F/0 to -999

°

C/0 to -999 Units

Default: -999

°

F

Alarm 2 Low: Represents the low process alarm or low deviation alarm for
Alarm 2. Appears if your unit has an auxiliary output and Ot4 = AL. See the model
number. If AL 2 = Pr:

Range: rL to A2HI

Default: rL

If AL 2 = dE: Range: 0 to -999

°

F/0 to -999

°

C/0 to -999 Units Default: -999

°

F.

Alarm 2 High: Represents the high process alarm or high deviation alarm for
Alarm 2. Appears if your unit has an auxiliary output and Ot4 = AL. See the model
number. If AL 2 = Pr:

Range: A2LO to rH

Default: rh

If AL 2 = dE: Range: 0 to -999

°

F/0 to -999

°

C/0 to -999 Units Default: -999

°

F

Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -99

°

F to 99

°

F/-55

°

C to 55

°

C/-99 Units to 99 Units; or -99.9

°

F to

99.9

°

F/-55.5

°

C to 55.5

°

C

Default: 0

Auto-Tune: This parameter initiates auto-tune for Output 1 in the heating mode
only. This parameter appears if Ot1 = ht. For more information on Tuning see
Chapter 6. Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Default: 0