beautypg.com

Output 1 wiring – Watlow Series 942 User Manual

Page 13

background image

13

Install and Wire, Chapter 2

WATLOW Series 942 User's Manual

Output 1 Wiring

Figure 16 -
Process, 4 - 20mA,
Output 1 Wiring.

Process, 4 - 20mA, Output 1

Model # 942A - _

F

_ _ - _ 000

Process Output
Proportional value determined by the control to balance the sensor input and set point. This
value will fall between 4 - 20mA depending on the thermal characteristics of the system.
Load impedance is 600

maximum.

Figure 17 -
Process, 0 - 20mA,
Output 1 Wiring.

Process, 0 - 20mA, Output 1

Model # 942A - _

G

_ _ - _ 000

Process Output
Proportional value determined by the control to balance the sensor input and set point. This
value will fall between 0 - 20mA depending on the thermal characteristics of the system.
Load impedance is 600

maximum.

Process, 0-20 mA, Non-Isolated

16

17

External

Load

+

-

I

DC

+

-

Process, 4-20 mA, Non-Isolated

17

18

External

Load

-

+

I

DC

-

+