Setup menuparameters/description, Setup – Watlow Series 942 User Manual
Page 27
Setup, Chapter 4
WATLOW Series 942 User's Manual
27
Setup
Use this page as a master copy for configuring your Series 942.
Do not enter any values here; make photocopies instead.
Setup Parameters
Value
Range
Factory Default
LOC
0 to 3
0
In
J, K (appears as H), t, n, c, r, S, b,
J or r
Pt2, rtd1, rtd.1, 0-5, 420
Dependent on model number.
dEC
0, 0.0, or 0.00
0
Dependent on input type.
C _ F
C or F
F
Will not appear if In = 0-5 or 420.
rL
rL to rH
Input selection dependent.
rH
rH to rL
Input selection dependent.
Ot1
ht or CL
ht
HYS1
1
°
F - 999
°
F, 1
°
C - 540
°
C, 1U - 999U
3
°
F
0.1
°
F - 99.9
°
F, 0.1
°
C - 54.0
°
C, 0.1U - 99.9U
Ot2
ht, CL or no
CL
HYS2
1
°
F - 999
°
F, 1
°
C - 540
°
C, 1U - 999U
3
°
F
0.1
°
F - 99.9
°
F, 0.1
°
C - 54.0
°
C, 0.1U - 99.9U
Ot3
AL, Ent or no
AL
AL1
Pr or dE
Pr
LAt 1
LAt or nLA
nLA
Dependent on AL 1 = Pr or dE.
HYS3
1
°
F - 999
°
F, 1
°
C - 540
°
C, 1U - 999U
3
°
F
0.1
°
F - 99.9
°
F, 0.1
°
C - 54.0
°
C, 0.1U - 99.9U
SIL
On or OFF
OFF
Ot4
AL, Ent, no, PrOC or StPt
AL or PrOC
AL 2
Pr or dE
Pr
LAt 2
LAt or nLA
nLA
HYS4
1
°
F - 999
°
F, 1
°
C - 540
°
C, 1U - 999U
3
°
F
0.1
°
F - 99.9
°
F, 0.1
°
C - 54.0
°
C, 0.1U - 99.9U
rtd
JIS or din
din
PtYP
ti or rAtE
ti
gSd
0 - 99
°
F, 0 - 55
°
C, 0 - 99U
0
0.0 - 9.9
°
F, 0.0 - 5.5
°
C, 0.0U - 9.9U
POUt
Cont, HOLd, Abrt or rSET
Cont
PStr
Proc or StPt
StPt
bAUd
300, 600, 1200, 2400, 4800, 9600
1200
dAtA
7 o = Odd parity, 7 E = Even parity
7 o
8 n = 8 data bits and no parity
Prot
FULL or On
FULL
Addr
0 to 31
0
Log
On or OFF
OFF
Int
0.0 to 60.0 minutes
0.0
tag
PSA, PS-, P-A, P--, -SA,
---
-S-, --A, ---
P = Process, S = Set point
A = Auxiliary Status
Table 2 -
Setup Menu Parametersand Descriptions.