beautypg.com

Solid state relay, output 1 wiring, Dc (open collector) output 1 wiring, Output 1 wiring – Watlow Series 942 User Manual

Page 12

background image

Install and Wire, Chapter 2

12

WATLOW Series 942 User's Manual

Output 1 Wiring

Figure 15 -
Process, 0 - 10VDC,
Output 1 Wiring.

Figure 14 -
6 Amp Mechanical
Relay, Output 1
Wiring.

Process, 0 - 10VDC, Output 1

Model # 942A - _

E

_ _ - _ 000

Mechanical Relay
The electromechanical relay is an electrical and mechanical device with moving parts.
When power is applied to the relay solenoid, contact closure is created through movement
of the "common" contact of the relay.
Off state impedance is 20K

minimum.

Mechanical Relay, 6 Amp, Form C, Output 1

Model # 942A - _

D

_ _ - _ 000

Mechanical Relay, Form C, 6 Amp

17

16

18

N.O.

COM.

External

Load

Fuse

L1

L2

N.C.

Process Output
Proportional value determined by the control to balance the sensor input and set point. This
value will fall between 0 - 10VDC depending on the thermal characteristics of the system.
Load impedance is 10K

minimum.

Process, 0-10VDC, Non-Isolated

16

17

External

Load

+

-

-

+

NOTE:
This output is sup-
plied with an arc
suppression snub-
ber across the out-
put terminals. High
impedance loads
may remain ener-
gized even though
the output device is
turned OFF.