Install and Wire, Chapter 2

10

WATLOW Series 942 User's Manual

Input Wiring

Figure 10 -
0 - 5VDC Process
Input Wiring.

NOTE:
When using a
4 - 20mA process
input, the input
impedance is 249

.

NOTE:
When using a
0 - 5VDC process
input, the input
impedance is
100K

.

Figure 11 -
4 - 20mA Process
Input Wiring.

1

2

3

+

-

DC

I

4 - 20mA Process Input

Model # 942A -

2

_ _ _ - _ 000

942A -

3

_ _ _ - _ 000

A jumper must be
installed between
Terminals #2 and 3.

0 - 5VDC Process Input

Model # 942A -

2

_ _ _ - _ 000

942A -

3

_ _ _ - _ 000

1

2

3

+

-

V

DC

When using a process input such as 0 - 5VDC or 4 - 20mA, the rL and rH settings scale the
display to match the measured range of the process signal.

An example of this is: A pressure transducer operates over a range of 0 - 300 PSI, delivering
a 4 - 20mA output signal for this range. By setting rL = 0 and rH = 300, the Series 942 now
displays a direct reading of pressure.