Chapter 4, Setup, How to setup the series 942 – Watlow Series 942 User Manual

Page 22: Entering the setup menu, The setup menu, Chapter 4 how to setup the series 942

background image

Setup, Chapter 4

22

WATLOW Series 942 User's Manual

Setup

Figure 33 -
The Setup Menu.

NOTE:
The rL and rH
parameters are used
to scale the display
for process inputs,
and/or will scale the
retransmit range for
process output. rL
and rH also limit the
ramge of the set
point.

M

= Parameter may or may not appear

depending on control configuration.

Entering the Setup Menu

The Setup Menu displays the parameters that configure the Series 942's features
to your application. Enter the Setup Menu by pressing the UP/DOWN keys simul-
taneously for 3 seconds. The Lower display shows the LOC parameter, and the
Upper display shows its current level. All keys are inactive until you release both
keys. You can reach the LOC parameter from anywhere except the Run menu.
While in the Setup menu, all outputs are OFF.

Use the MODE key to cycle through the menu, and the UP/DOWN keys to select
Setup data. You will not see all parameters in this menu, depending on the unit's
configuration, model number, and LOC parameter. After stepping through the
menu it returns to the control set point parameter under the Operation menu.

Chapter 4

How To Setup The Series 942

Setting up the Series 942 is a simple process. First configure the 942's features to
your application in the Setup Menu, enter values in the Operating Menu, and pro-
gram your control. Use the MODE key to move through the menus and the UP/
DOWN keys to select data. At this point, enter the Calibration menu, and select US
or SI under the dFL parameter if necessary. Rate, reset and

°

F appear with US,

and integral, derivative and

°

C appear with SI. See Appendix III.

Figure 32 -
Entering the Setup
Menu.

[SP]

Loc

In

dEC

C_F

rL

rH

Ot1

HYS1

Ot2

HYS2

Ot3

AL1

LAt1

HYS3

SIL

Ot4

AL2

LAt2

HYS4

rtd

PtYP

gSd

Pout

bAUd

dAtA

Prot

Addr

LOg

Int

tAg

User lock out

Input type

Decimal place

Celcius_Fahrenheit

Range low

Range high

Output 1

Hysteresis 1

Output 2

Hysteresis 2

Output 3

Alarm 1

Latching for alarm 1

Hysteresis 3

Silence alarm

Output 4

Alarm 2

Latching for alarm 2

Hysteresis 4

RTD calibration curve

Program type

Guaranteed soak deviation

Power outage

Baud rate

Data bits and parity

Protocol type

Address

Logging printout

Time interval

Variables to transmit

[Set Point]

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

PStr

Profile start