General Specifications

„ Electrical Specifications

„ Environmental Specifications

„ Structural Specifications

Po

wer Supp

ly

Input Voltage

DC24V

Rated Voltage

DC19.2 to 28.8V

Allowable Voltage
Drop

5ms (max.)

Power Consumption 26W (max.)

In-Rush Current

30A (max.)

Voltage Endurance

AC1000V 20mA for 1 minute (between charging and FG terminals)

Insulation Resistance

DC500V 10M

Ω (min.) (between charging and FG terminals)

Phy

s

ic

al

Surrounding Air
Temperature

0 to 50

°C

Storage Temperature

-20 to +60

°C

Ambient Humidity

10 to 90% RH (Wet bulb temperature: 39°C max. - no
condensation.)

Storage Humidity

10 to 90% RH (Wet bulb temperature: 39°C max. - no
condensation.)

Dust

0.1mg/m

3

and below (non-conductive levels)

Pollution Degree

For use in Pollution Degree 2 environment.

Ins

tal

lation

Grounding

Grounding resistance of 100

Ω, 2mm

2

or thicker wire, or your

country’s applicable standard.
(Same for FG and SG terminals)

Structure

*1

*1 The front face of the GP unit, installed in a solid panel, has been tested using conditions equivalent to

the standards shown in the specification. Even though the GP unit’s level of resistance is equivalent to
these standards, oils that should have no effect on the GP can possibly harm the unit. This can occur in
areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere
to the unit for long periods of time. If the GP’s front face protection sheet becomes peeled off, these
conditions can lead to the ingress of oil into the GP and separate protection measures are suggested.

Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel’s plastic
cover. Therefore, prior to installing the GP be sure to confirm the type of conditions that will be present
in the GP’s operating environment.

If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from
the panel, the original level of the protection cannot be guaranteed. To maintain the original protection
level, be sure to replace the installation gasket regularly.

Rating: IP65f NEMA #250 TYPE 1
(Front surface at panel embedding)
Feature size: All-in-one
Installation configuration: Panel embedding

Cooling Method

Natural air circulation