Ap pen dix e: trou ble shooting 42, Troubleshooting 42, Troubleshooting – Maple Systems MAP450D User Manual

Page 43: Appendix e, The oit will not enter configuration mode

background image

APPENDIX E

Troubleshooting

When Power is Applied the OIT’s Display is Blank and the OIT

Beeps

This indicates that the OIT does not contain a complete project and that the OIT is in

download mode waiting for STEPware-100 to download a project. Refer to the STEP1

Protocol Operation Manual

-

Chapter 1: Getting Started for instructions on creating and

downloading a STEPware-100 project.

The OIT Will Not Enter Configuration Mode

If, instead of displaying Parameters? MODIFY, the OIT displays Disp View Angle: or

Baud Rate:, Local Setup Access has been disabled. You will need to enable Local Setup

Access by connecting the OIT to a host controller and having the host controller send the

Keyboard control command to the OIT. Refer to Appendix A: Control Commands for

more information.
If, for some reason, you cannot reenable the Local Setup Access using the Keyboard

Control command, perform the following:

1. While pressing and holding down the CLEAR or ENTER key, cycle power to the

OIT. Continue pressing until the OIT displays Disp View Angle:, then release.

2. Press the ENTER key to display the Baud Rate: message.
3. Press the B key.
4. Press the I key.
5. Press the P key.
6. Wait for a few seconds. The OIT will reinitialize, allowing you to enter Local Setup

by holding down the CLEAR or ENTER key.

7. Refer to Chapter 1: OIT Configuration and follow the instructions.

Appendix E: Troubleshooting

42

1010-0101, Rev. 00