background image

Operating Mode Setting

This parameter determines whether the OIT operates in Interactive, Block, or Network

mode. Refer to Chapter 2: Operating Modes for more information.
Factory Default: Interactive
To modify this parameter using STEPware-100:
1. Open the Configuration Editor.

2. In the OIT Operational Settings group box, select the desired operating mode from

the Operating Mode option buttons.

To modify this parameter in Configuration mode:
1. At Op Mode:, use the OIT’s Period (.) key to select the desired operating mode. Refer

to the Configuration Mode section in this chapter for more information.

To modify this parameter from the host controller:
1. Use the Set Operating Mode control command. Refer to Appendix A: Control

Commands for more information.

Line Terminator Setting

This parameter determines which ASCII control character is used for the line terminator.

Options are CR, LF, CR/LF, or ETX. The line terminator performs different functions in

Interactive, Block, and Network modes. In all three modes, the line terminator is sent to

the host controller when the OIT responds to a control command and when the OIT’s

ENTER key is pressed.
In Interactive mode, if local echo is enabled when the OIT’s ENTER key is pressed, the

line terminator is also sent to the OIT’s display. In Block or Network mode, if block echo

is enabled when the OIT’s ENTER key is pressed, the line terminator is also sent to the

OIT’s display. In Network mode, the line terminator is used to indicate that the host

controller has finished communicating to a particular OIT. The line terminator, therefore,

notifies the other terminals that the next two bytes received from the host controller

indicate which OIT the host controller wants to talk to.
Refer to Chapter 2: Operating Modes for more information on the use of the line

terminator in Interactive, Block, and Network modes.
Factory Default: CR
To modify this parameter using STEPware-100:
1. Open the Configuration Editor.
2. In the OIT Operational Settings group box, select the desired line terminator from the

Line Terminator option buttons.

To modify this parameter in Configuration mode:
1. At Line Term:, use the OIT’s Period (.) key to select the desired line terminator. Refer

to the Configuration Mode section in this chapter for more information.

To modify this parameter from the host controller:
1. Use the Set Line Terminator control command. Refer to Appendix A: Control

Commands for more information.

Chapter 1: OIT Configuration

10

1010-0101, Rev. 00