Vanguard ATRT-03_03B User Manual
Page 77
ATRT-03, ATRT-03A, AND ATRT-03B USER’S MANUAL
REV 7
71
f. Start from the “START-UP” menu again to run a test using the loaded test plan from the
previous steps:
Press the
[1]
key (TEST XFMR).
g. The following screen will be displayed (test details will differ depending on the test type
defined in the test plan):
NOTE
The above screen will be displayed only if a test plan is loaded first.
Press the
[1]
key (CONTINUE).
h. The following screen will be displayed:
Press the
[1]
key (NO).
i. The following screen will be displayed:
Set the transformer to the tap position indicated on the LCD screen. Press the
[START]
key to run the test using the test plan.
j. The unit will start performing the test and the screen will be updated with the test
results as shown:
RATIO mA % DIFF
+10.022 0012 0.10P
+10.005 0011 0.06P
+10.023 0017 0.11P
TAP NUMBER 1
H VTG: 1,734
X VTG: 100
“START” to RUN TEST
STOP BETWEEN PHASES?
1.NO
2.YES
#1 Y-DELTA TAPS:20
TEST PLAN LOADED
1.CONTINUE
2.UNLOAD TEST PLAN
1.TEST XFMR 08/23/10
2.SETUP 08:25:15
3.CALCULATOR
4.DIAG 5.QUICK TST