Relay Menus
The Relay menus (Relay 1 through Relay 4) are used to configure the X96S relay outputs. These four relay menus show
the settings of the corresponding relay output and allow the characteristics of the output to be changed. Each menu contains the
following items:
ITEM
FUNCTION
Source
Shows, and allows the user to set, the source
Alarm Type
Shows, and allows the user to set, the alarm type
Setpoint
Shows, and allows the user to set, the alarm set point
Setpoint2
Shows, and allows the user to set, the second alarm set point
5
Hysterisis
Shows, and allows the user to set, the alarm hysterisis percent
Polarity
Shows, and allows the user to set, the alarm polarity
Alarm Source is one of the following:
Alarm Source
MEANING
Level
Operate relay when Level is in alarm as defined the Alarm Type and set points.
HeadTemp
Operate relay when the head temperature is in alarm as defined by the Alarm Type and
set points
System Alarm
Operate relay when the X96S detects a problem
Detector Flt
Operate relay when a there is a problem with detector
Rad Disc
Operate relay when the Rad. Disc. function triggers.
Auto Cal Ref
Operate relay when the X96S is performing an automatic calibration
Auto Cal Err
Operate relay if the X96S detects an error while performing an automatic calibration
Not Used
This relay is not currently in use.
Alarm Type is one of the following:
Alarm Type
MEANING
None
Alarm not yet set
Low
Alarm when the source is equal to or lower than Setpoint
High
Alarm when the source is equal to or higher than Setpoint
Range
Alarm when the source is equal to or lower than Setpoint or equal to or higher
than Setpoint2
Polarity is one of the following:
Polarity
MEANING
NO
Normally open
NC
Normally closed
TTL Menus
The TTL menus (TTL 1 through TTL 4) are used to configure the X96S TTL outputs. These four TTL menus show the settings
of the corresponding TTL output and allow the characteristics of the output to be changed. Each menu contain the following
items:
ITEM
FUNCTION
Source
Shows, and allows the user to set, the source
Alarm Type
Shows, and allows the user to set, the alarm type
5
The second alarm set point is only used when the alarm type is range.