MICROPAK NODE ADAPTER PLC I/O

(Cont.)

- Node per Bell Mode

DISCRETE OUTPUT

CONFIGURATION

Discrete Output

Word Configuration

Word

0
1

(Not Used)
Discrete Output Bits*

* Reference “Discrete Output Bit

Definition” chart.

HV On Command
HV Reset
Fluid Trigger / Di/dt Delay
Air Trigger
Di/dt Inhibit

MicroPak #1
MicroPak #1
MicroPak #1
MicroPak #1
MicroPak #1

Output

Bit

Module

00
01
02
03
04

DISCRETE OUTPUT BIT DEFINITION

BTW Word

Module

0
1
2
3
4

MicroPak
MicroPak
MicroPak

(Not Used)

Atomizer

High Voltage Setpoint (Value of 0-100 corresponds to 0-100 kV)
Current Limit Setpoint (Value of 0-250 corresponds to 0-250 µA*)
Di/dt Setpoint ( 0 - 9 corresponds to max. to min. sensitivity)
----
Speed Command Liquid (Value of 0-50 corresponds to 0-50 krpm)

Speed Command Powder (Value of 0-150 corresponds to 0-15 krpm)

BLOCK TRANSFER WRITES

BTW Block Configuration

Module

0
1
2
3
4
5

MicroPak
MicroPak
MicroPak

Atomizer
Atomizer
Atomizer

High Voltage Feedback (Value of 0-100 corresponds to 0-100 kV)
Current Feedback (Value of 0-250 corresponds to 0-250 µA

+

)

MicroPak Status Word*
Atomizer Status Word**
Atomizer Drive Pressure (Value of 0-60 corresponds to 0-60 psi)
Atomizer Speed Liquid (Value of 0-50 corresponds to 0-50 krpm)

Atomizer Speed Powder (Value of 0-150 corresponds to 0-15 krpm)

BTR Block Configuration

BLOCK TRANSFER READS

BTR Word

* 0-85 corresponds to 0-85 µA for HP404 FM

0-1000 corresponds to 0-1000 µA for RP1000 or LEPS5002 applications.

* Reference “MicroPak Status Word” table.

** Reference “Atomizer Status Word” table.