beautypg.com

Operation, Ransburg, Operator control – Ransburg MicroPak LECU5004 User Manual

Page 16: Modes of operation / configuration

background image

MicroPak - Operation

Ransburg

13

LN-9218-00.13

OPERATOR CONTROL

Operator control may be accomplished by:
(1) front panel controls

(2) CANBus serial communication

(3) node adapter

(4) discrete analog and digital I/O

1. Front panel controls are provided for power on,

high voltage set point, over current set point, di/

dt sensitivity, and high voltage on/off.

2. CANBus connection provides expanded

control and monitor functions shown as analog

in/out and discrete in/out in the MicroPak Spec-

ifications.

3. Node Adapter connection converts an external

serial protocol, such as Allen-Bradley Remote I/O,

to CANBus for communication to the MicroPak.

The format for Allen-Bradley communication is

shown under “MicroPak Node Adapter PLC I/O”

in the “Operation” section of this manual.

4. Discrete I/O connections are made via the

76111-xx I/O cable which connects to connector

J12. The 76111 connector must be secured to

the J12 connector shroud by the two screws on

the connector body. The pin-out of the discrete

signals begins on page 14.

The Discrete I/O Module switch SW2, position 1

must be set for the cascade in use with the Mi-

croPak. For RP1000 or LEPS5002 application,

SW2-1 is OFF. For HP404, RP404 and HP505

application, SW2-1 is ON.

OPERATION

MODES OF OPERATION /

CONFIGURATION

(Refer to Figure 6)

Local / Remote

The Local/Remote switch located on the front panel

determines the source for the setpoints for kV, di/

dt and Over Current. In the Local Position, these

come from the front panel controls labeled kV and

µA. In the Remote position, these come from the

Node Adapter, directly from CANBus, or from the

Discrete I/O Module, except as described below.

The MicroPak can be configured for a fixed (in-

ternal adjustment) µA (overload) setpoint while

accepting a remote analog kV setpoint. To enable

this feature, see figure 6. In this configuration,

the µA setpoint comes from pot R21 at the top of

the Process PCB instead of the external analog

signal. Holding in the “SET” button will display

the analog kV setpoint and the fixed (internal) µA

setpoint.

HV Cascade / Regulation Mode

The MicroPak is factory configured for HP404,

RP404, or HP505 cascade applications or ap-

plications using the 74793-XX or LEPS5002 HV

units. In addition, the cascades may be operated

in voltage regulation or current regulation modes.

Each configuration has a specific part number as

shown in the “Parts Identification” section of this

manual.

HV On Control Remote

When remote HV On controls are used, SW3-3

should be set to ON. Motherboard terminal J6-3

should be jumpered to J6-2 to enable the HV

Ready mode.