beautypg.com

Ransburg, Micropak - operation, Determining if a di/dt overload occurred – Ransburg MicroPak LECU5004 User Manual

Page 19: Voltage boost mode, Voltage regulation, Current regulation

background image

MicroPak - Operation

Ransburg

16

LN-9218-00.13

To Read the Di/dt Setting

Push the “SET” push-button twice within one

second. The kV display will read “SLP” and the

µA display will indicate a number between 0 and

9. This number represents different levels of di/

dt sensitivity with 0 being most sensitive. If the

“SET” push-button is not pressed again, the µA

display will automatically return to normal output

current display.

To Adjust the Di/dt Value

Local Mode

Once a di/dt sensitivity level is displayed, it can

be changed by pressing the “SET” button again

and holding in. The sensitivity level will increment

slowly. Once the desired level is displayed (0-9),

then release the “SET” button. The new value is

stored in memory when the “SET” push-button is

released. This setting should be set as sensitive

as possible (smallest di/dt value) without nuisance

overloads occurring. This should be done with

paint loaded and normal production parts present.

Remote Mode

In remote mode, the above sensitivity levels are

set by the numbers 0 to 9 in a Block Transfer

Write (BTW) similiar to the method for setting the

setpoint for kV. The BTW information is shown

in the “MicroPak Node Adapter PLC/IO” in the

“Operation” section.

The di/dt sensitivity level in Minimized Remote

Mode (Remote mode where SW3-1 is in OFF

position) will still be set as in Local mode. In this

mode, the kV setpoint is still remote, and the µA

setpoint is still from internal pot R21.

The di/dt function can be inhibited when needed

during the application process to avoid nuisance

shutdown. To understand the details of using

this feature with either the Discrete I/O Module

or Serial Node Adapter, reference the appropriate

I/O tables further back in this Operation section.

Determining if a Di/dt

Overload Occurred

The “OVER” LED (overload) will flash on and off if

a di/dt caused an overload, otherwise the “OVER”

LED will stay on continuously if a fixed current

overload occurred. This will help determine the

type of high voltage fault that occurred.

Voltage Boost Mode

The MicroPak software has been revised to provide

two voltage correction modes when configured for

the HP404 cascade. The purpose of this change

is to compensate for the voltage drop in the cas-

cade’s current limiting resistor.

Position 1 (see Figure 6), voltage correction 1

mode, provides correction when the output current

is always below 50 µA. Position 2 (see Figure 6),

voltage correction 2 mode is the default mode and

provides correction when the output current runs

or may range above 50 µA.

Voltage Regulation

To date, the most common type of output regulation

for electrostatic painting applications is voltage

regulation. This means sensing the output volt-

age, comparing this to the voltage setpoint, and

adjusting the cascade drive to maintain the output

equal to the setpoint. In this mode the current

varies, depending on the load, up to the Current

Setpoint where the unit switches to Over Current,

turning off the output.

Current Regulation

The MicroPak is also capable of current regu-

lation which is desired for some applications. In

this mode the functions of voltage and current are

reversed from the voltage regulation mode. This

means sensing the output current, comparing this

to the current setpoint, and adjusting the cascade

drive to maintain the current output equal to the

current setpoint. In this mode the voltage varies,