Operation – Fulton Pulse HW (PHW) Fully Condensing Hydronic Boiler User Manual
Page 56

© The Fulton Companies 2013
OPERATION
PHW-IOM-2013-0214
SECTION 3
3-20
5. Back out to the Confi gure Screen and press Sensor Confi guration. The
“sola” password will need to be entered. Press the Outdoor temperature
source and choose EnviraCOM outdoor source. See Figure 49.
NOTE: The 1ea (KIT) 2-40-001072, outdoor sensor and Interface Module is
required, wired to the Sola base ECOM terminals 1,2, and 3.
FIGURE 49 - SENSOR CONFIGURATION
6. Back out to the Confi gure menu and press Verify and complete the
verifi cation process. See Figure 50.
FIGURE 50 - VERIFICATION
!