Operation – Fulton Pulse HW (PHW) Fully Condensing Hydronic Boiler User Manual

Page 49

background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 3

PHW-IOM-2013-0214

OPERATION

3-13

!

CAUTION

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

FIGURE 33 - SENSOR CONFIGURATION SCREEN

FIGURE 34 - MODULATION

than what may be required. The boiler will shut off at this setpoint if
remote contacts are not opened.

NOTE: Selecting Burner On/Off will require remote on/off (stop/start) contacts.

Procedure for Remote Setpoint Using a 4-20mA Signal (Single

Boiler)

1. From the Status Summary Screen press Confi g, arrow down to and press

Sensor Confi guration. Choose S2 (J8-6) Sensor, this will require the
sola password. Choose 4-20mA. See Figure 33. This will also require a
verifi cation. See High Water Temperature Limit section for verifi cation
steps.

2. In Central Heat Confi guration in the Modulation screen, the Modulation

Rate Source must be Local. See Figure 34.

3. In Central Heat Confi guration in the Setpoint screen, change Setpoint

source to S2 (J8-6) 4-20mA; and change the 4mA Water Temperature and
20mA Water Temperature to the required setting. See Figure 35.