SECTION 2
VTG-IOM-2013-0815
INSTALLATION
2-13
burner confi gurations do not support vent limiters and
will need to be vented if required by the AHJ.
17. Vantage boilers with the SKP25 fuel train are in
compliance with CSD1 and CSA. This confi guration is
also compliant with IRI, which has been replaced by GE
GAP. NFPA 85 confi guration is available as an option to
comply with local codes or regulations that specifi cally
require a vent valve.
18. Please note that custom confi gurations or other off
standard projects may utilize alternate fuel trains. For
these situations, refer to submittal drawings.
19. Ensure the burner will be supplied with suffi
cient
ventilation and uncontaminated air for proper
combustion. Air contaminants include, but are not
limited to, chlorides, halogens, fl ourocarbons, and
construction dust. Refer to appropriate jurisdictional
codes.
Components Requiring Ventilation to the
Outdoors
Although there are custom fuel train requirements available
that do not include components requiring ventilation to the
outdoors, many Vantage fuel trains will require a vent line on
the gas pressure regulator.
Follow the recommendations of the manufacturer of the
gas pressure regulator for specifi c instructions. General
TABLE 3 - NOMINAL PIPE SIZE
Nominal
Pipe Size
ID
Equivalent Pipe Length
Max Capacity in ft3 of natural gas per hour. Pressure drop of
0.5”wc/Equivalent length of pipe (feet)
Inch (mm)
Inch (mm)
90 Elb
Feet
(meter)
Tee
Feet
(meter)
20
40
60
80
100
150
200
1-1/4 (31.75)
1.380 (35.05)
3.45 (1.05)
6.9 (2.10)
950
-----
-----
-----
-----
-----
-----
1-1/2 (38.1)
1.610 (40.89)
4.02 (1.22)
8.04 (2.45)
1460
990
810
-----
-----
-----
-----
2 (50.8)
2.067 (52.50)
5.17 (1.57)
10.3 (3.13)
2750
1900
1520
1300
1150
950
800
2-1/2 (63.5)
2.469 (62.71)
6.16 (1.87)
12.3 (3.74)
4350
3000
2400
2050
1850
1500
1280
3 (76.2)
3.068 (77.92)
7.67 (2.33)
15.3 (4.66)
7700
5300
4300
3700
3250
2650
2280
4 (101.6)
4.026 (102.26)
10.10 (3.07)
20.2 (6.15)
15800
10900
8800
7500
6700
5500
4600
6 (152.4)
6.07 (154.17)
10.10 (3.07)
23.60 (7.19)
-----
-----
-----
-----
20200
16503
12766
8 (203.2)
7.98 (202.69)
13.30 (4.05)
29.10 (8.86)
-----
-----
-----
-----
41200
33660
29128
FIGURE 6 - FULTON PH NEUTRALIZING KIT (WITHOUT PUMP)