beautypg.com

Micromod RetroPAK: SLC Installation Manual User Manual

Page 47

background image

SLC RetroPAK Controller

POWER, GROUNDING, AND BUILT-IN I/O CONNECTIONS

23

5. Use a small flat-head screwdriver to loosen appropriate connection screws and clamps

on terminal blocks.


6. Strip approximately 5/16 inch (8 mm) of insulation from the end of each wire, insert wires

at assigned terminals and secure terminal screws and clamps.


7. Make wiring connections using the following procedures:


a. Power connections - Section 3.3.

b. Ground and shield connections - Section 3.4.

c. Built-in process input connections for various types of inputs - Section 3.5

d. Built-in output connections - Section 3.6


8. After all connections are completed and checked, do the following:


a. If modular I/O and communications are required, follow the procedures in Sections 4

and 5.


b. If all connections are completed, the ac power wiring can be connected at the

distribution panel (ac source).


NOTE: Before putting the controller into operation, it must be configured using Visual
Application Designer software. See Section 1.1.2 for related documents.

Common should not be left floating. Tie it to chassis or a separate instrument ground if

available.

NOTES TO FIGURE 3-1:
1. CONTROLLER SUPPLIES LOOP POWER FOR ALL AI SHOWN.
2. LAND RTD, T/C OR 4-WIRE INPUTS ON BUILT-IN CHANNELS 1, 2.
3. NEMA 1 CONTROLLER STYLE, BUILT IN RS-232 FOR LAPTOP CONFIG.
4. FOR PERMANENT PC CONNECTION, CHG JUMPER, USE TERMS 1-5.
5. DIGITAL IN / OUT ARE WETTED BY EXTERNAL 24 VDC P / S.

This manual is related to the following products: