beautypg.com

Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual

Page 38

background image




Remote I/O Modules

ELECTRICAL CONNECTIONS

Technical Characteristics

General

Power supply

24 VDC

230 VAC/120 VAC

Number of inputs per unit

8 max.

8 max.

Number of outputs per unit

8 max.

8 max.

Power supply isolation

no

1500 VAC

Maximum power consumption
without load on the outputs

0.2 A

10 VA

Maximum power dissipation

6 W

8 W


Inputs

Signal level, nominal value

24 VDC

24 VDC

Input opto-isolated

no

no

Signal level of the input

0 - OFF signal

– 3 V to + 5 V

– 3 V to + 5 V

1 - ON signal

+ 15 V to + 30 V

+ 15 V to + 30 V

Open circuit detection

yes

yes

Input current, nominal value (under 24 VDC)

6 mA

6 mA

Input delay

8 ms

8 ms


Outputs

Process supply

24 VDC

24 VDC

Output opto-isolated

no

no

Maximum voltage drop under nominal load

3 V

3 V

Residual current for 0 signal

< 1 mA

< 1 mA

Switching frequency with inductive loads

max. 0.1 Hz

max. 0.1 Hz

Maximum current

0.5 A

0.5 A

Lamp loads

5 W

5 W

Total current for 8 outputs

max. 2 A

max. 2 A

Short-circuit protection (I

> 2 A)

yes yes

Overload protection (I

> 0.6 A, t > 250 ms)

yes yes

Open circuit detection (I

< 50 mA)

yes yes

34