beautypg.com

1 icsi 08 d1 - 8 non-isolated 24vdc inputs, Remote i/o modules electrical connections – Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual

Page 19

background image



Remote I/O Modules

ELECTRICAL CONNECTIONS

3.6.1 ICSI 08 D1 - 8 Non-Isolated 24Vdc Inputs

Binary non isolated input unit with 8 input channels for 24 VDC. The unit has to be mounted
on a plug-in base ECZ.
Description:
Eight yellow input status led's «0» to «7»

1

«TEST» push-button .......... 2

Red error led ...................... 3

List of error codes .............. 4

Electrical Connection:
• Common “+” terminals are connected together.
• Common “+” terminals must not be used when the unit’s power supply is 24 VDC.
• Common “+” terminals may be used to supply the inputs with 24 VDC when the unit’s

power supply is 120/230 VAC.

• If an external power supply 24 VDC is used for inputs, the "0" VDC must be connected to

the common "".

Caution: 24 VDC must never be connected to common "+".

3

2

4

I/O REMOTE UNIT

ICSI08D1 120 VAC

Unit error

Bus error

TEST

0

1

2

3

4

5

6

7

0

1

2

3

1

4

5

6

7

Input

8

9

10

11

12

13

14

15

Cut Wire

ABB Procontic CS 31

Shield

Bus # 1

Bus # 2

Common +

Common -

Common -

A

B

C

D

E

F

G

H

Common +

Common +

Common +

Common +

Common +

Power
Supply

230 VAC

120 VAC

15