beautypg.com

Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual

Page 35

background image



Remote I/O Modules

ELECTRICAL CONNECTIONS

Technical Characteristics

General

Power supply

24 VDC

230 VAC/120 VAC

Number of inputs per unit

12

12

Number of outputs per unit

8

8

Isolated power supply

no

yes (1500 VAC)

Maximum consumption

0.3 A

10 VA


Inputs
Signal level of the input, nominal value

24 VDC

24 VDC

0 - OFF signal

–3 to +5V

–3 to +5V

1 - ON signal

+15 to +30V

+15 to +30V

Opto isolated inputs

no

no

Input current for 24 VDC

5 mA

5 mA

Input delay

8 ms

8 ms


Outputs

Opto isolated outputs

yes

yes

Switching capacity under 2 A (

resistive or

inductive load)

120/230 VAC 50/60Hz

2 A

2 A

DC

60 W (2A)

60 W (2A)

Nominal current

2 A AC-1

2 A AC-1

Minimum power for the contacts

12 VDC 10 mA

12 VDC 10 mA

24 VDC internal power supply

no

yes (

±5%) 100 mA

Total current Common M-Q

120/230 VAC 50/60Hz

6 A

6 A

24 VDC

6 A

6 A

Total current Common R-T

120/230 VAC 50/60Hz

4 A

4 A

24 VDC

4 A

4 A

Short-circuit protection

no

no

Over voltage protection

Varistor

Varistor

31