Remote I/O Modules
ELECTRICAL CONNECTIONS
3.4
REMOTE I/O INTERFACE BUS CONNECTIONS
The remote I/O Interface (CS 31) bus is a shield twisted pair RS485 connected as described
below. One 2020N Remote I/O Interface module is required for each remote I/O network.
REMOTE I/O INTERFACE RS485 SERIAL NETWORK
Bus Master
2020N Remote I/O Interface Module (end of bus)
Bus Slaves
Remote I/O Digital Modules
Maximum Length
500 meters (1600 feet)
Baud
Rate
187.5K
Number of Addresses 32 (31 slaves + 1 RIO master at address 0). Star connection
of the bus is forbidden!
Termination
120
Ω, 1/4 Watt resistor required across the two conductors
at each end of the cable (2 shipped with RIO module)
Shield
Required over 50 meters (160 feet). The shield of the bus
must be connected to the earth near the master. The shield
is connected to the earth through a capacitor 1 nF class Y.
Isolation
The bus is opto-isolated from all units.
REMOTE I/O INTERFACE CABLE
Indoor
Beldon
#9182
Indoor
Plenum
Beldon
#89182
Underground
Beldon #9815 twisted twinax
Outdoors above ground NOT recommended
Wiring
See
connection
guidelines
When noisy elements are in the area of the cabinet, it is better to connect the bus' shield to
the ground via a capacitor 1 nF class Y directly at the access of the cabinet according the
following diagram.
11