Table 4-4. analog output (ano) module – Micromod Micro-DCI: 53ML5100 Manual Loader User Manual
Page 37
53ML5100B Manual Loader
INSTRUCTION MANUAL
33
Table 4-4. Analog Output (ANO) Module
Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the displayed percent
and to select the analog input signal (ANI0-3) that is to be routed to the analog output (ANO0).
Title
Symbol
ANO0
Datapoint
Default
Attribute
Analog Output
(Display Only)
ANO0
ANO1
C000
C001
0
0
The value in this datapoint represents the percent of
output to be generated by hardware (e.g., 100% output
= 20 mA).
0 -20 mA
Output
OZBASE0
OZBASE1
L472
L473
0
When a 0, the percentage output generates a 4 -20 mA
signal. When set to 1 , the percentage output generates
a 0 -20 mA signal.
Calibrate Zero
COZ0
COZ1
B267
B268
Calibrate
Span
COS0
COS1
C300
C301
These parameters are factory set and should not
need adjustment under normal operation. See Section
5.3 for adjustment.
Reverse Valve
RSV0
RSV1
L109
L133
0
0
Positions the forward/reverse valve indicators
(C for close, O for open) beneath the output
horizontal bar graph of each Manual Loader with
Analog Input Display (Channel 1 and Channel
2). When set to a 0, it indicates 20 mA output opens the
valve (C at left end and O at right end of bar graph).
When set to a 1, it indicates 20
mA output closes the valve (O at left end and C
at right
end of bar graph).
Control Action
L106
L130
0
0
When set to a 0, current increases toward 20
mA to open the valve more as the output indicator
increases when the push button is pressed.
When set to a 1, current decreases toward 0 mA
to
close the valve as the output indicator
increases when
the push button is
pressed.
Engineering
Units
A001
A003
PERCENT
(Both)
Assignable for units of measure the ANO
represents (e.g., GPM for gallons per minute).
Tag Name
AOTAG0
AOTAG1
A244
A245
ANO0
ANO1
The assignable 10 character name for for each ANO
(ANO0 and ANO1).