Table 4-4. Analog Output (ANO) Module

Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the displayed percent
and to select the analog input signal (ANI0-3) that is to be routed to the analog output (ANO0).
Title

Symbol

ANO0

Datapoint

Default

Attribute

Analog Output
(Display Only)

ANO0
ANO1

C000
C001

0
0

The value in this datapoint represents the percent of
output to be generated by hardware (e.g., 100% output
= 20 mA).

0 -20 mA
Output

OZBASE0
OZBASE1

L472
L473

0

When a 0, the percentage output generates a 4 -20 mA
signal. When set to 1 , the percentage output generates
a 0 -20 mA signal.

Calibrate Zero

COZ0
COZ1

B267
B268

Calibrate
Span

COS0
COS1

C300
C301

These parameters are factory set and should not
need adjustment
under normal operation. See Section
5.3 for adjustment.

Reverse Valve

RSV0
RSV1

L109
L133

0
0

Positions the forward/reverse valve indicators
(C for close, O for open) beneath the output
horizontal bar graph of each Manual Loader with
Analog Input Display (Channel 1 and Channel
2). When set to a 0, it indicates 20 mA output opens the
valve (C at left end and O at right end of bar graph).
When set to a 1, it indicates 20
mA output closes the valve (O at left end and C

at right

end of bar graph).

Control Action

L106
L130

0
0

When set to a 0, current increases toward 20
mA to open the valve more as the output indicator
increases when the push button is pressed.
When set to a 1, current decreases toward 0 mA

to

close the valve as the output indicator

increases when

the push button is

pressed.

Engineering
Units

A001
A003

PERCENT

(Both)

Assignable for units of measure the ANO
represents (e.g., GPM for gallons per minute).

Tag Name

AOTAG0
AOTAG1

A244
A245

ANO0
ANO1

The assignable 10 character name for for each ANO
(ANO0 and ANO1).