3 engineering mode overlays, 1 responding to the prompt: key, Ngineering – Micromod Micro-DCI: 53ML5100 Manual Loader User Manual
Page 28: Verlays, Responding to the prompt: key
53ML5100B Manual Loader
INSTRUCTION MANUAL
3.3 Engineering Mode Overlays
The engineering mode overlays are used to make the necessary parameter entry selections for the operator
displays and to configure the Datalink communications port. The entries are made to addressed datapoints
via the overlay single edit line at the bottom of the display. It should be noted that engineering mode has a 20
second timeout if it is accessed and its functions (e.g., configure or display) are not used.
3.3.1 Responding to the Prompt: KEY?
When the password prompt KEY? appears, it indicates a password was set in the MicroTools software. The
password can not be set via the front panel push buttons.
A password key is a maximum of 10 numeric characters (numbers 0-9 only). It does not impede display
functions in engineering mode but must be unlocked to perform configuration functions. A password key is
NOT SET FOR NEW INSTRUMENTS from the factory; therefore, if it is set, it must have been done locally.
The password must first be obtained from the originator before the procedure in Table 3-1 can be used to
access the engineering mode configuration function capabilities.
Table 3-1. Entering a Key Password
Step
Press
Once
Shift
Result
Press to
Locate
Target
Char.
Result
1
Puts instrument in engineering mode.
2
If DISPLAY appears instead of CONFIGURE, press 2.
3
F3
Displays password query: KEY?
4
2
Puts first password number on entry line: KEY? .2.
5
.2Δ
2
Shifts 2 and puts second password number on entry
line: KEY? .22.
6
.22Δ
2
Shifts 22 and puts third password number on entry
line: KEY? .222.
7
Repeat step 6 until all of the password characters are entered.
8
F3
Enters the password key and displays the entry line:
POINT . The engineering mode configuration
function is now accessible for use.
NOTE:
Δ indicates Space
24