15.5 First-Time Startup and Verification Test:

1.

Turn ON the UPS input circuit breaker.

2.

Verify that the UPS output circuit breaker and the battery circuit breaker on
the battery cabinet both remain OFF.

3.

Press twice on the UPS ON/OFF button on the
P

OWER

+

SA front panel.

ON/OFF button

4.

Turn ON the Battery circuit breaker on the battery cabinet.

5.

Verify that

• The messages “UPS ON” and “NORMAL MODE” appear on the LCD

screen.

• The LEDs “AC INPUT” and “NORMAL” are lit.
• All other LEDs are off.

6.

Perform a manual battery test as described in Section “Manual Battery Test” on
page 43 to verify the condition of the battery and that it is properly connected
to the UPS.

7.

Turn ON the UPS Output circuit breaker.

Risk of electrical shock!

Input/Output voltage is present on the terminals.

8.

The UPS is ready to take the load. Ask the equipment operator to turn on the
devices connected to the UPS.

9.

Look at the Main Screen and verify that the UPS is loaded by the customer’s
equipment. The LCD on the UPS front panel should display the percentage of
power being consumed by the load from each input phase.

POWER+ SA User Guide (UL), Release 1.0

74