beautypg.com

Troubleshooting, Alarm sounds and/or alarm led lights up, Battery test failed – MaxPower Corp Gamatronic Power+ SA User Manual

Page 69: The ups remains in bypass mode, Sync fault

background image

Gamatronic Electronic Industries Ltd.

14. TROUBLESHOOTING

This section explains what to do in the event of an alarm condition, or when any other
“out of the ordinary” event occurs on the UPS.

Alarm sounds and/or alarm LED lights up

1.

Go to the Event Log and look at the Active Alarm Display to determine the
nature of the alarm. See “Navigating to the Event Log” and “Active Alarm
Display” on page 36.

2.

Look for the appropriate heading below according to the nature of the alarm,
and follow the instructions.

Electricity returned but UPS remains in battery mode

Check the external circuit breaker for the AC line. The circuit breaker may be off.

Battery test failed

It may be that an automatically scheduled battery test was executed shortly after the
end of a power outage, when the battery was still charging. Wait until about two hours
after the return of the AC power and perform a manual battery test. This should clear
the alarm.

The UPS remains in bypass mode

The UPS may have been put in bypass mode manually. In such a case, the lower left
quadrant of the Main Screen says “manual bypass”. To manually return the UPS to
normal mode, see “Manually entering or leaving bypass mode” on page 58

Sync Fault

Verify that the AC Input and the Bypass Input lines are connected to the UPS in
proper phase sequence.
Verify that AC of the proper frequency (Hz) is being used. (See on page 83.)

POWER+ SA User Guide (UL), Release 1.0

63