To install the battery and prepare it for initial UPS start-up:

1.

Verify that the battery circuit breaker is OFF and that the UPS is OFF, and that
there is no power on the UPS cables.

2.

Position the battery box as described in section 15.2.2, “Equipment Location”,
on page 65.

3.

Remove the front panel from the battery box. See

Figure 15-6

.

4.

On the P

OWER

+

SA, run the battery cable through the cable holder labeled

“Batteries”, shown in Figure 15-3 on page 69. Attach the cable to the UPS’s
“Battery” terminals as labeled in Figure 15-8 above. The other end of the
battery cable must be attached to the battery box terminals as labeled in Figure
15-7 above
.

5.

Tighten the cable holder holding the battery cable on the UPS.

6.

Replace the cover of the battery box terminals.

Continue to the next section.

15.4 Verifications Prior to First-Time Operation

After connection of the P

OWER

+

SA and its batteries as described in sections 15.3.2

and 15.3.3 and before first-time use, the following verifications must be performed.

1.

Verify that the AC input cables from the external power source to the UPS
Input are connected and fastened securely. (Follow and verify the phase
sequence.)

2.

Verify that the AC output cables from UPS to the load are connected and
fastened securely. (Follow and verify the phase sequence.)

3.

Verify that the cable between the UPS’s battery terminals and the batteries is
correctly and securely connected on both ends.

4.

Verify that any additional control wiring is run in individual, separate conduits.

5.

Verify that all power connections are tight.

6.

Verify that all control wire terminations are tight.

7.

Verify that all power wires and connections have proper spacing between
exposed surfaces, phase-to-phase, and phase-to-ground.

8.

Replace the protective cover over the terminal connectors on the P

OWER

+

SA

and on the battery box.

POWER+ SA User Guide (UL), Release 1.0