MaxPower Corp Gamatronic Power+ SA User Manual
Page 47
Gamatronic Electronic Industries Ltd.
User Guide
ONE PHASE FAULT
Meaning:One or more of the AC phases into the Charger is out of range.
Additional indications The alarm LED lights up and the audible alarm
sounds.
Action: This is likely to be due to a problem with the input AC supply.
OVERLOAD
Meaning:There is an overload condition.
Additional indications The alarm LED lights up and the audible alarm
sounds. If the output current is between 104 – 117%, for 10 minutes, or
between 117 – 131% for one minute, or above 131% for 20 msec, the UPS
shuts down. The symbol
appears on the Main Screen.
Action: Reduce the load to the UPS quickly, or the UPS will automatically
move to Bypass mode.
+
41
POWER SA User Guide (UL), Release 1.7